SupportsDF32-L1PCI,DFPROFI,DFPROFIIIandFNL
OPCisafascinatingtechnologywithalmostunlimitedpossibilities.OPCstandsfor OLEforProcessControl anddefinesthecommunicationbetweenarbitraryWindows2000applicationsonthebasisofMicrosoftDCOM,specializedfortherequirementsinthefieldofprocessautomation.
TheobjectiveofOPCistherandomcombinationofWindowsstandardproductsfromtheautomationandprocesscontrolareawithoutcustomization,suchasdriverdevelopmentorintegration.
AnOPCclientaccessesthedataofanOPC-Serverviatheservertags.Withdata,whichisassignedtotheseservertagsfromtheprocessperiphery.Thistechnologyworksnetwork-wide.
TodayalmostallautomationandvisualizationsystemsareequippedwithanintegratedOPC-client-interface,allowingeasyconnectiontoaprocessperipherywithOPC-Servertechnology.
Thismakesthedevelopmentofspecialdriversorintegrationobsolete.Standardproductscanbecombinedarbitrarily.
TheCOMSOFTOPC-ServerisbasedontheDFboardsandtheFNLandsupportstheprotocolsSINEC-L1andPROFIBUSDP/DPV1.
TheserverwasdevelopedaccordingtothelatestspecificationsoftheOPCfoundation.Itsupportsallinterfacesofversions1.0Aand2.0andisimplementedinthefreethreading/multithreadingmodel,guaranteeingoptimumperformance.
Apowerfulconfigurationtoolisincludedinthescopeofdelivery.Itcanbeusedforthesettinginoperationoftheconnectedcommunicationlineandfordefinitionoftherequiredservertags.
Theintegratedtestanddiagnosistoolsallowfastandefficienttroubleshooting.AlsoincludedisanexampleofanOPC-clientapplication,inordertotesttheactualserverconfigurationwithregardstofunctionality.
FortheuseofPROFIBUSDP/DPV1inacontinuouslyrunningsystem,likeinprocessengineeringapplications,theCOMSOFTserversupportsdynamicmodificationsofthecurrentconfigurationunderconditionsofcontinuousdataflow.
ThePROFIBUSstructurecanbechangedorextendedatanytimewithoutinterruptingtheongoingdatatransfer.
ThecommunicationdirectedviatheOPCserverisconfigureddynamicaly.Thecontinuousoperationisassured.
TransmissionProtocols
PROFIBUSDP/DPV1(master,slave)
SINEC-L1(master,slave)
OpcConfigurator
ProcessDataRouting
Theconfigurationtoolallowsanassignmentofprocessdatatocommunicationobjects(tags)oftheOPC-servers.Sincetheassignmentisrealizedonabitlevel,alldataformatsarepossible(Bit,Byte,Int,Long,Float,BCDetc.).Therefore,theeffortontheOPC-Clientlevelfortheencodingofspecialprocessdataisreducedtoaminimum.
Functions:TestandStart-up
Theconfigurationtoolsfeaturecompletefunctionsforparametersettingandstart-up,aswellasforthetestingoftheconnectedcommunicationline.IfPROFIBUSDP/DPV1isused,thefollowingadditionalfunctionsareavailable:
Automaticrecognitionandconfigurationoftheconnectedbusunits
InterpretationoftherespectiveGSD-files,parameterizationandconfigurationoftheDP-Slaveswiththerespectivedata
ExtensivetesttoolsfordataexchangewiththeconnectedDP-slaves.AllDP/DPV1servicesaresupported.Allparameterscanbeeditedseparately.